TNMS Controller Client
communication driver
TNMS Controller Client
communication driver is the
driver to communicate with invert of
TNMS Controller.
<Figure 1> is read setting example of
TNMS_Client communication driver.
<Figure 1> Read setting example of TNMS_Client communication driver
Device part of <Figure 1> input Device type(TCP/IP), IP
address of PLC(1
1. Read Settings
In protocol option part, you can set the IP address( default = 192.168.1.46 ) of client system.
TNMS Controller Client communication driver read schedule
TNMS Controller Client communication driver's read schedule input 'READ' and device ID one line.
Read schedule example)
READ,
18,
The TNMS Controller Client communication driver periodically sends a connection request packet and does not store it separately in memory because it receives only the request response.
You can set TNMS system by using 'write settings'.
Digital Write
Digital write and analog write have the same setting parameters except output value.
Analog Write
Analog write setting parameters are as follows:
1) PORT port no. (0 ~ 255)
2) STATION station number of controller.
3) ADDRESS not
used.
4) Extra1
error location(6digit ), error type(3digit ), error grade(1digit ), error code number(5digit ) Input by dividing by dots(.).5) Extra2
not used.6) Value 1 = failure alarm, 0 = clear alarm.
Write example 1)
PORT : 0 STATION : 18 ADDRESS : 0000 EXTRA1 : MODULE.UPS.2.12345 EXTRA2 : 0
If this is set and analog output is made, the TNMS server connected to port 0 will be faulty.Generate failure alarm (value of 1) or disable (failure) of position = MODULE, fault type = UPS, fault class = 2, fault code number = 12345 (Output value of 0).<see Figure 3>
<Figure 3> Example of TNMS Controller Client write settings.